JUMO dTRANS T06 Multifunctional Four-Wire-Transmitter in Mounting Rail Case

Description

Short description
The transmitter acquires the temperature through an RTD temperature probe or a thermocouple (double thermocouple). The transmitter can also acquire standard signals. Connection takes place through an RTD temperature probe with two-wire, three-wire, or four-wire connection.

Available models

  • Type 707071: Functionally expandable through the extra code, relay output and an RS485 interface.
  • Type 707071/8-XX-058: Device fulfills the requirements of SIL 2 / SIL 3 in accordance with DIN EN 61508 and PL c / PL d in accordance with DIN EN ISO 13849 as well as the requirements of DIN EN 60730-2-9.

Often sold accessories

  • Setup Software dTRANS T06 Series
  • USB cable, A plug to Micro B plug

Benefits

  • Universal input for a large number of sen- sors and standard signals
  • Intuitive operation and configuration on the device or through a USB interface with set- up program
  • RS485 interface Modbus RTU and relay output limit value (optional)
  • Intelligent additional functions such as min./ max. drag indicator, operating hours count- er, and output simulation
  • SIL 2 / SIL 3 in accordance with DIN EN 61508 and PL c/d in accordance with ISO 13849 (optional)
  • Sensor matching for RTD temperature probes
  • Customer-specific linearization
  • High galvanic signal separation
  • Service and operation hours counter
  • Connection diagram retrievable in the dis- play

 

Environmental influences-10 to +70 °C
Output signal0(2) to 10 V or 0(4) to 20 mA (reversible)
ParticularitiesRS485 interface Modbus RTU and relay output limiter(option), intelligent additional functions such as min./max. Operating hours counter and output simulation.
CertificatesSIL en PL, cUL, DNVGL
BrandJUMO
Voltage supplyAC 110 to 240V, DC 24V (four-wire measuring transducer)
Accuracy±0.05%
InstallationOn mounting rail/DIN rail 35 × 7.5 mm
NAMUR compliantNE43
ConfigurationOn the device via USB interface with PC setup program
Analog inputResistance thermometer in 2-, 3- and 4-wire circuit; thermocouple, double thermocouple; resistance potentiometer/WFG; resistance/potenti in 2-, 3- and 4-wire circuit; voltage 0 to 1(10) V; current 0(4) to 20 mA
Gavanically separated1,8 Kv